High temperature Hepa filters

Poliven HT 120ºC

The HEPA absolute filters are used for filtration of inlet, outlet and recirculation air in ventilation systems such as: Clean Rooms, Operating Theatres, Laboratories, etc., Industrial Processes: Microelectronics, food Industry, optics, pharmaceutical, fine chemistry, etc. Treatment of dangerous substances: Asbestos, Metal dust, Bacteria, Viruses, Radioactive Particles.

Technical features

Type: Compact Multihedral Absolute Filter with Very High Efficiency and Large Flow.
Frame: Galvanized Steel, with handle
Filtering Element: Glass microfiber paper.
Separators: Glue beads Higt Temperature.
Sealant: Polyurethane.
Gasket: Bicomponent polyurethane liquid system. (Semi-circular expanded polyurethane)
MPPS efficiency: 85%, 99.95% and 99.995%
EN 1822 Class: E10, H13 and H14.
Recommended Final Pressure Loss: 600 Pa.
Temperature: 120-145ºC in continuous service.

Advantages

– High Nominal airflow flow for a low pressure Drop.
– Filters totally interchangeable with separator filters minipleat and with Galvanized steel or wooden frames.

Category

High Temperature Filters

Certificates

Poliven HT 120ºC

References

*UxP: Units per box *Stock
F: Manufacture, S: Stock, SL: Limited Stock