Box Panel Filters

Varipac

Panel Filters for Air Handling units (Autonomous Conditioners, Air Conditioning Ventilation units, Industrial Processes (Pharmaceutical, Microelectronics, Optics, Food, Veterinary, Fine Chemicals, Industry.)

Technical features

Type: High Efficiency Compact Filter.
Frame: Galvanized Steel/Plastic.
Filtering Element: Fiberglass paper.
Separators: Thermoplastic glue beads.
Sealant: Polyurethane.
Clamp or flange: Galvanized Steel.
Gasket: liquid system of bi-component polyurethane.
Average Efficiency % (Em): 40% ≤ Em < 60%, 60% ≤ Em < 80%, 80% ≤ Em < 90%, 90% ≤ Em < 95% and 95% ≤ Em
EN 779 Class: M6, F7, F8 and F9.
ISO 16890: ePM2.5 50%, ePM1 50%, ePM1 65% and ePM1 80%.
Recommended Final Pressure Loss: 450 Pa.
Temperature: 80ºC in continuous service.

Advantages

– The V-shaped pleating method guarantees the optimum geometrical form of the pleats and a uniform
distance between them. This allows to get the same filtering area as with the aluminum separators filters in
order to obtain the same airflows, similar pressure losses and the same filtration efficiency.
– V-shaped pleat technology ensures that aluminum separators may be removed eliminating the risk
of leaks due to perforations in the aluminum separators.
– The filter is light and it is used in narrow spaces. (135 mm.)
– The uniform shape of the pleats ensures that the airflow does not generate turbulences.
– Ref. VPP have a flange or trawe that adapts to pre-existing frames in the installations without making any
modifications for new installations. The appropriate frames are the BRTM type.
– Plastic frame.
– Ref. VP has no flange and has a depth of 150 and 292 mm., For new installations the suitable racks are BTRA type.
– Galvanized steel flange.

Category

Air treatment

Certificates

Graphic

FUNCTION OF PRESSURE DROP VS. FLOW RATE
VPP - WITH CLAMP
VPP - WITHOUT CLAMP

Varipac

References

* ME%: Minimum Efficiency EN779: 2012
* Energy Consumption kWh / year: Calculated according to Eurovent 4 / 21-2017 guidelines.
** Energy Consumption kWh / year: Calculated according to Eurovent guidelines.
**** Energy class according to Eurovent.

*UxP: Units per box